Comparative study on the power quality of public grid, solar, and wind energy systems

dc.contributor.authorGandorj, Enkhjin
dc.contributor.authorPurvee, Ariunbolor Prof. Dr.
dc.contributor.authorVandandorj, Ankhbayar
dc.date.accessioned2026-11-24T03:43:00Z
dc.date.issued2026
dc.descriptionBachelor's thesis submitted to the German-Mongolian Institute for Resources and Technology (GMIT), Study program: Energy and Electrical Engineering. Supervisor 1 / Examiner 1: Prof. Dr. Ariunbolor Purvee. Supervisor 2 / Examiner 2: Mr. Ankhbayar Vandandorj. Ulaanbaatar/Nalaikh, 2026.
dc.description.abstractThis paper compares power quality attributes across three generation/supply systems currently active in the Mongolian Central Energy System (CES): the public distribution grid (powered by coal/CHP), a utility-scale solar photovoltaic plant, and a wind energy plant. On-site measurements were taken at each facility using a Baker EXP4000 Dynamic Motor Analyzer, and interpreted relative to Mongolian national standard MNS 1778:2007, as well as the Unified Energy Grid Rules (2021). At each site we analyzed five parameters defined by MNS 1778:2007: steady state voltage deviation (δUy), voltage total harmonic distortion (KU), per-order harmonic coefficients (KU(n)), negative-sequence voltage unbalance (K2U), and frequency deviation (Δf). For all five parameters, all three grids remain within MNS 1778:2007 prescribed maxima. Voltage deviation is above normal levels of ±5% at the public (+7.13%) and solar PV (+6.33%) sites, but within the ±10% maximum; the wind farm site shows +2.97% and falls within normal range. Total harmonic distortion comes in at 0.80% (public), 2.20% (solar PV), and 1.60% (wind); all three easily within the 8% normal maximum. Dominant order is the 13th harmonic (650 Hz) at both renewable sites, as would be expected from six-pulse PWM inverter function at partial load. Triplen harmonics are essentially non-existent at any of the sites. Frequency deviation was measured to be precisely 0 at all three sites. Key findings include ongoing voltage overvoltage at low-voltage points of connection, likely the result of inappropriate transformer tap settings rather than injection from renewables, and the absence of current harmonic limits in Mongolia's incomplete power quality standards regime — MNS 1778:2007 currently only defines limits for voltage harmonics. We make recommendations for corrective tap adjustments, reactive power compensation where necessary, continuous power quality monitoring, and establishment of a companion standard to MNS 1778:2007 for current harmonics. By providing the first side-by-side MNS 1778:2007-compliant power quality measurement across all three forms of electricity generation currently in Mongolia's CES, we hope to establish a quantitative benchmark against which future measurements can be compared as renewables are added in increasing quantities to meet the national target of 30% renewable generation.
dc.identifier.otherB2200224
dc.identifier.urihttps://gmitlibrary.net/handle/123456789/261
dc.language.isoen
dc.publisherGerman-Mongolian Institute for Resources and Technology
dc.subjectPower quality
dc.subjectMNS 1778:2007
dc.subjectHarmonics
dc.subjectVoltage deviation
dc.subjectSolar PV
dc.subjectWind
dc.subjectMongolia
dc.subjectBaker EXP4000
dc.subjectTHD
dc.subjectVoltage unbalance
dc.titleComparative study on the power quality of public grid, solar, and wind energy systems
dc.typeThesis

Files

Original bundle

Now showing 1 - 1 of 1
No Thumbnail Available
Name:
Enkhjin_Gandorj_Bachelor_Thesis.pdf
Size:
1.75 MB
Format:
Adobe Portable Document Format

License bundle

Now showing 1 - 1 of 1
No Thumbnail Available
Name:
license.txt
Size:
1.71 KB
Format:
Item-specific license agreed to upon submission
Description:

Collections